HCA-4 - 4 Zone Conventional Panel, 6.5 AMP, 120V, Red
The HCA series is available in a 2, 4, or 8 zone conventional panel design which is in accordance with UL 864 9th Edition Listing Detection and Fire Alarm Systems – Control and Indicating Equipment. STANDARD FEATURES • UL864 9th Edition / NFPA Compliant • Fully programmable using simple menu options • Built-in two-line (16 Characters for each line) LCD display provides easy to read information • 15 Key control buttons for easy programming, reset and silencing. • Real time clock • Event History log (256 events) with Date/Time stamp, which can be viewed from LCD display • Compatible with wide range of detection devices • 4 Programmable Supervised NAC outputs • Switchable 120/240VAC 50/60 Hz Power supply • 5 Programmable output patterns for NAC circuits • Gentex Sync Protocol Built-in • Built-in Dialer for HCA-2D, HCA-4D and HCA-8D Only • Supports Releasing of Agents & Water on HCA-4 & HCA-8 models • Three programmable general purpose relays • Dedicated alarm and trouble relays • Built-in walk test feature • Supports up to two 12V, 18Ah Backup batteries • Supports one Remote Annunciator via RS-485